PRO AV CATALOG
End-of-Line Speaker Load Modules for Supervision
Series: Atlas
Model: IED5410EOL/IED5411EOL
- For proper/complete speaker line testing, speakers on a circuit must be wired as one continuous string without any paralleled off branches
- Only one 5410EOL/5411EOL can be applied to the end of the speaker line of any one DZM speaker output
- Not permissible to place additional units in branch circuits of the same speaker output
- 5410EOL-For use with amplifiers producing less than 200W (continuous) or use with the output of the 5432DZM
- 5411EOL-For use with amplifiers producing 200W (continuous) or more
For proper/complete speaker line testing, speakers on a circuit must be wired as one continuous string without any paralleled off branches. The figure below shows the right and wrong ways to interconnect speakers for proper testing. Only one 5410EOL/5411EOL can be applied to the end of the speaker line of any one DZM speaker output. It is not permissible to place additional units in branch circuits of the same speaker output.
- For proper/complete speaker line testing, speakers on a circuit must be wired as one continuous string without any paralleled off branches
- Only one 5410EOL/5411EOL can be applied to the end of the speaker line of any one DZM speaker output
- Not permissible to place additional units in branch circuits of the same speaker output
- 5410EOL-For use with amplifiers producing less than 200W (continuous) or use with the output of the 5432DZM
- 5411EOL-For use with amplifiers producing 200W (continuous) or more
- Spec Sheet available - Yes
- Operating Temperature (Maximum): 212 F
- Operating Temperature (Minimum): -40 F
- Width: 0.96 in
- Color: Black
- 5410EOL: use with amplifiers producing less than 200W (continuous) or use with the output of the 5432DZM
- 5411EOL: use with amplifiers producing 200W (continuous) or more
- Test Limits:
- Test Tone (measured at the output of the amplifier)
- V <= 15 Volts: May be applied continuously
- f = 20 kHz
- V >15 Volts: Thermal limited,
- f = 20 kHz 100°C: ±5%
- Test Tone (measured at the output of the amplifier)
- Maximum Test Tone Voltage: 100 V
- Connectors: Flying Leads
- Length: 1.96"
- Thickness, not including leads: 1.0"
- Lead length: 6" Measured from top surface
- Storage Temperature Range: –58° F to +221° F (–50° C to +105° C)
Suggested Products
Advanced Sound & Communication
3817 Broadway
Kansas City, MO 64111
USA
(816) 931-9525
www.advancedsoundkc.com